Air Conditioners for Electrical Cabinets
IP Enclosures air conditioners are highly efficient air conditioners specifically designed for the cooling needs of electrical enclosures. They are available as IP54 for indoor applications, and IP55 for outdoor applications. Air Conditioning is required when the internal temperature is required to be lower than ambient temperature and for high heat loads. IP Enclosures air conditioners are designed for dissipation of heat from inside electrical enclosures and data racks. Air conditioning is based on the heat exchange between two separate air circuits. Air circulation inside the enclosure is separated from external ambient air, protecting the contents of the enclosure from dust and moisture. In the first circuit, heated air is circulated from inside the enclosure to the air conditioning unit and returns chilled into the enclosure. In the second circuit, ambient air circulates from outside the enclosure to the air conditioning unit and returns to outside. The air conditioner digital thermostat is factory set at 35°C and is adjustable from 20°C to 45°C. The evaporator fan operates continuously to circulate internal air, ensuring a uniform distribution of temperature inside the cabinet, preventing hot spots. When the temperature inside of the enclosure is higher than the set-point value, the refrigeration cycle starts. When the internal temperature decreases below set point value, the refrigeration cycle stops. To ensure efficient flow and to prevent flow being directed at active components, a flow diverter accessory should be used. To prevent dirt and dust from entering the air conditioner internal components, an air conditioner filter may be fitted. IP Enclosures Air Conditioners are made in Italy and are SAA approved and certified for use in Australia. In line with IP Enclosures’ focus on providing protection, our range of air conditioners aim to support the directive of ever-decreasing GWP (Global Warming Potential) Index. Contact our electrical enclosure specialists for assistance to calculate the required cooling output (Watts) of air conditioners.
IP Enclosures Air Conditioners are provided with a built-in digital thermostat providing the following functionality:
- Set temperature of compressor start
- Set temperature of compressor shutdown
- Set delay on/off of compressor in terms of temperature
- Set time of compressor to avoid intermittent on/off
- Set maximum value for overcoming maximum temperature in the cabinet, after which thermostat emits an alarm
- Set delay time of alarm switch
- Door interlock
- RS485 connection interface
REQUEST PRICE & AVAILABILITY
Our sales team will send a quote for this product. Please complete details below and a quote will be sent as soon as possible. Thankyou.
Select the Right Air Conditioners
Use the Electrical Enclosure & Cabinet Thermal Calculator
Size | IP54 INDOOR | IP55 OUTDOOR | ||||||
---|---|---|---|---|---|---|---|---|
Watts | SKU | Data Sheet | Template | Step File | SKU | Data Sheet | Template | Step File |
350 Watts | IP-ACIWM035 | .stp | IP-ACOWM035 | .stp | ||||
850 Watts | IP-ACIWM085 | .stp | IP-ACOWM085 | .stp | ||||
1450 Watts | IP-ACIWM145 | .stp | IP-ACOWM145 | .stp | ||||
2000 Watts | IP-ACIWM200 | .stp | IP-ACOWM200 | .stp | ||||
3000 Watts | IP-ACIWM301 | .stp | IP-ACOWM300 | .stp | ||||
4000 Watts | IP-ACIWM401 | .stp | IP-ACOWM400 | .stp |
Indoor IP54 Wall-Mounted Air-Conditioner Details
Vertical-mount compact IP54 air conditioners are specifically designed for the cooling needs of indoor electrical cabinets. They are optimised for door or side-panel mounting and have been designed for high efficiency and low maintenance. The corrosion resistant Stainless Steel (304) option for harsher environments is categorised by the ‘.0X’ product code.
350W
IP-ACIWM035 – 350W Indoor Wall Mounted Air Conditioner
Features | Unit | IP-ACIWM035 | |
---|---|---|---|
Power supply | V/Hz | 230V/1ph/50-60 | |
Dimensions HxWxD | mm | 430x280x170 | |
Cooling capacity EN814 A35A35 | W | 350/370 | |
Cooling capacity EN814 A35A50 | W | 200/220 | |
Air fow rate (free blow) | |||
inside | m³/h | 350/390 | |
outside | m³/h | 600/625 | |
Max current | A | 1.8/1.9 | |
Delayed fuse | A | 4 | |
Absorbed electric power EN814 A35A35 | W | 260/270 | |
Absorved electric power EN814 A35A50 | W | 280/300 | |
Refrigerant (type/charge) | g | R134a/300g | |
Maximum Pressure | kPA | 2400 | |
Operating temperature (ambient) | °C | +20/+55 | |
Operating temperature (enclosure) | °C | +20/+45 | |
Temperature controller (factory set at 35°C) | – | Integrated mechanical thermostat | |
Compressor type | – | Rotative compressor | |
Noise level | dB(A) | 60 | |
Electrical connection | – | Three-pole connector | |
Protection degree EN60529/1 enclosure inside | – | IP54 | |
Protection degree EN60529/1 ambient inside | – | IP34 | |
Weight (with packaging) | kg | 15(16) | |
Colour | – | RAL 7035 | |
Conformity/Certifications | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
850W
IP-ACIWM085 – 850W Indoor Wall Mounted Air Conditioner
Features | Unit | IP-ACIWM085 |
---|---|---|
Power supply | V/Hz | 230V/1ph/50-60 |
Dimensions HxWxD | mm | 635x305x210 |
Cooling capacity EN814 A35A35 | W | 850/900 |
Cooling capacity EN814 A35A50 | W | 625/650 |
Air flow rate (free blow) | ||
inside | m3/h | 600/625 |
outside | m3/h | 600/625 |
Max current | A | 2.65/2.75 |
Delayed fuse | A | 6 |
Absorbed electric power EN814 A35A35 | W | 450/470 |
Absorbed electric power EN814 A35A50 | W | 530/560 |
Refrigerant (type/charge) | g | R134a/390g |
Maximum Pressure | kPA | 2400 |
Operating temperature (ambient) | °C | +20/+55 |
Operating temperature (enclosure) | °C | +20/+45 |
Temperature controller (factory set at 35°C) | – | Integrated mechanical thermostat |
Compressor type | – | Rotative compressor |
Noise level | dB(A) | 62 |
Electrical connection | – | Three-pole connector |
Protection degree EN60529/1 enclosure inside | – | IP54 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | Kg | 23(24) |
Colour | – | RAL 7035 |
Conformity/Certifications | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
1450W
IP-ACIWM145 – 1450W Indoor Wall Mounted Air Conditioner
Features | Unit | IP-ACIWM145 |
---|---|---|
Power supply | V/Hz | 230V/1ph/50-60 |
Dimensions HxWxD | mm | 800x400x240 |
Cooling capacity EN814 A35A35 | W | 1450/1500 |
Cooling capacity EN814 A35A50 | W | 1150/1200 |
Air flow rate (free blow) | ||
inside | m3/h | 600/625 |
outside | m3/h | 880/950 |
Max current | A | 3.7/4.2 |
Delayed fuse | A | 6 |
Absorbed electric power EN814 A35A35 | W | 650/700 |
Absorbed electric power EN814 A35A50 | W | 770/850 |
Refrigerant (type/charge) | g | R134a/700g |
Maximum Pressure | kPA | 2400 |
Operating temperature (ambient) | °C | +20/+55 |
Operating temperature (enclosure) | °C | +20/+45 |
Temperature controller (factory set at 35°C) | – | Integrated mechanical thermostat |
Compressor type | – | Rotative compressor |
Noise level | dB(A) | 65 |
Electrical connection | – | Three-pole connector |
Protection degree EN60529/1 enclosure inside | – | IP54 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | Kg | 37(38) |
Colour | – | RAL 7035 |
Conformity/Certifications | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
2000W
IP-ACIWM200 – 2000W Indoor Wall Mounted Air Conditioner
Features | Unit | IP-ACIWM200 |
---|---|---|
Power supply | V/Hz | 230V/1ph/50-60 |
Dimensions HxWxD | mm | 1000x400x240 |
Cooling capacity EN814 A35A35 | W | 2000/2100 |
Cooling capacity EN814 A35A50 | W | 1200/1250 |
Air flow rate (free blow) | ||
inside | m3/h | 600/625 |
outside | m3/h | 880/950 |
Max current | A | 6.6/6.9 |
Delayed fuse | A | 10 |
Absorbed electric power EN814 A35A35 | W | 1060/1100 |
Absorbed electric power EN814 A35A50 | W | 1240/1300 |
Refrigerant (type/charge) | g | R134a/600g |
Maximum Pressure | kPA | 2400 |
Operating temperature (ambient) | °C | +20/+50 |
Operating temperature (enclosure) | °C | +20/+45 |
Temperature controller (factory set at 35°C) | – | Integrated mechanical thermostat |
Compressor type-Alternative compressor | ||
Noise level | dB(A) | 70 |
Electrical connection | – | Three-pole connector |
Protection degree EN60529/1 enclosure inside | – | IP54 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | Kg | 49(50) |
Colour | – | RAL 7035 |
Conformity/Certifications | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
3000W
IP-ACIWM300 – 3000W Indoor Wall Mounted Air Conditioner
IP-ACIWM300.0X- 3000W Stainless Steel Indoor Wall Mounted Air Conditioner
Features | Unit | IP-ACIWM300/IP-ACIWM300.0X |
---|---|---|
Power supply | V/Hz | 400V/3ph/50-460V3ph/60 |
Dimensions HxWxD | mm | 1500x400x255 |
Cooling capacity EN814 A35A35 | W | |
Cooling capacity EN814 A35A50 | W | |
Air flow rate (free blow) | ||
inside | m3/h | 600/625 |
outside | m3/h | 880/950 |
Max current | A | 2.2/2.6 |
Delayed fuse | A | 16 |
Absorbed electric power EN814 A35A35 | W | |
Absorbed electric power EN814 A35A50 | W | |
Refrigerant (type/charge) | g | R134a/600g |
Maximum Pressure | kPA | 2400 |
Operating temperature (ambient) | °C | +20/+50 |
Operating temperature (enclosure) | °C | +20/+45 |
Temperature controller (factory set at 35°C) | – | Integrated mechanical thermostat |
Compressor type-Alternative compressor | ||
Noise level | dB(A) | 70 |
Electrical connection | – | Three-pole connector |
Protection degree EN60529/1 enclosure inside | – | IP54 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | Kg | 49(50) |
Colour | – | RAL 7035 |
Conformity/Certifications | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
4000W
IP-ACIWM400 – 4000W Indoor Wall Mounted Air Conditioner
IP-ACIWM400.0X- 4000W Stainless Steel Indoor Wall Mounted Air Conditioner
Features | Unit | IP-ACIWM400/IP-ACIWM400.0X |
---|---|---|
Power supply | V/Hz | 400V/3ph/50 – 460V/3ph/60 |
Dimensions HxWxD | mm | 1500x400x255 |
Cooling capacity EN814 A35A35 | W | 3800/3980 |
Cooling capacity EN814 A35A50 | W | 2800/3160 |
Air flow rate (free blow) | ||
inside | m3/h | 600/625 |
outside | m3/h | 880/950 |
Max current | A | 2.7/3.0 |
Delayed fuse | A | 16 |
Absorbed electric power EN814 A35A35 | W | 2200/2320 |
Absorbed electric power EN814 A35A50 | W | 2600/2750 |
Refrigerant (type/charge) | g | R134a/600g |
Maximum Pressure | kPA | 2400 |
Operating temperature (ambient) | °C | +20/+50 |
Operating temperature (enclosure) | °C | +20/+45 |
Temperature controller (factory set at 35°C) | – | Integrated mechanical thermostat |
Compressor type-Alternative compressor | ||
Noise level | dB(A) | 70 |
Electrical connection | – | Three-pole connector |
Protection degree EN60529/1 enclosure inside | – | IP54 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | Kg | 49(50) |
Colour | – | RAL 7035 |
Conformity/Certifications | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
Outdoor IP55 Wall-Mounted Air-Conditioner Details
Vertical-mount compact outdoor IP55 air conditioners are specifically designed for the cooling needs of outdoor electrical cabinets. They are optimised for door or side-panel mounting and have been designed for high efficiency and low maintenance. Outdoor models include a special cover designed to protect internal components, a condenser fan controller and pressure controller for the compressor. The outdoor range has been designed to provide protection in the harshest outdoor conditions. The corrosion resistant Stainless Steel (304) option is categorised by the ‘.OX’ product code.
350W
IP-ACOWM035 – 350W Outdoor Wall Mounted Air Conditioner
Features | Unit | IP-ACOWM035 |
---|---|---|
Power supply | V/Hz | 230V/1ph/50-60 |
Dimensions HxWxD | mm | 430x280x170 |
Cooling capacity EN814 A35A35 | W | 350/370 |
Cooling capacity EN814 A35A50 | W | 200/220 |
Air fow rate (free blow) | ||
inside | m³/h | 350/390 |
outside | m³/h | 600/625 |
Max current | A | 1.8/1.9 |
Delayed fuse | A | 4 |
Absorbed electric power EN814 A35A35 | W | 260/270 |
Absorved electric power EN814 A35A50 | W | 280/300 |
Refrigerant (type/charge) | g | R134a/300g |
Maximum Pressure | kPA | 2400 |
Operating temperature (ambient) | °C | +5/+55 |
Operating temperature (enclosure) | °C | +20/+45 |
Temperature controller (factory set at 35°C) | – | Integrated mechanical thermostat |
Compressor type | – | Rotative compressor |
Noise level | dB(A) | 60 |
Electrical connection | – | Three-pole connector |
Protection degree EN60529/1 enclosure inside | – | IP55 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | kg | 15(16) |
Colour | – | RAL 7035 |
Conformity/Certifications | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
850W
IP-ACOWM085 – 850W Outdoor Wall Mounted Air Conditioner
Features | Unit | IP-ACOWM085 |
---|---|---|
Power supply | V/Hz | 230V/1ph/50-60 |
Dimensions HxWxD | mm | 635x305x210 |
Cooling capacity EN814 A35A35 | W | 850/900 |
Cooling capacity EN814 A35A50 | W | 625/650 |
Air flow rate (free blow) | ||
inside | m3/h | 600/625 |
outside | m3/h | 600/625 |
Max current | A | 2.65/2.75 |
Delayed fuse | A | 6 |
Absorbed electric power EN814 A35A35 | W | 450/470 |
Absorbed electric power EN814 A35A50 | W | 530/560 |
Refrigerant (type/charge) | g | R134a/390g |
Maximum Pressure | kPA | 2400 |
Operating temperature (ambient) | °C | +5/+55 |
Operating temperature (enclosure) | °C | +20/+45 |
Temperature controller (factory set at 35°C) | – | Integrated mechanical thermostat |
Compressor type | – | Rotative compressor |
Noise level | dB(A) | 62 |
Electrical connection | – | Three-pole connector |
Protection degree EN60529/1 enclosure inside | – | IP55 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | Kg | 23(24) |
Colour | – | RAL 7035 |
Conformity/Certifications | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
1450W
IP-ACOWM145 – 1450W Outdoor Wall Mounted Air Conditioner
Features | Unit | IP-ACOWM145 | |
---|---|---|---|
Power supply | V/Hz 230V/1ph/50-60 | ||
Dimensions HxWxD | mm | 800x400x240 | |
Cooling capacity EN814 A35A35 | W | 1450/1500 | |
Cooling capacity EN814 A35A50 | W | 1150/1200 | |
Air flow rate (free blow) | |||
inside | m3/h | 600/625 | |
outside | m3/h | 880/950 | |
Max current | A | 3.7/4.2 | |
Delayed fuse | A | 6 | |
Absorbed electric power EN814 A35A35 | W | 650/700 | |
Absorbed electric power EN814 A35A50 | W | 770/850 | |
Refrigerant (type/charge) | g | R134a/700g | |
Maximum Pressure | kPA | 2400 | |
Operating temperature (ambient) | °C | +5/+55 | |
Operating temperature (enclosure) | °C | +20/+45 | |
Temperature controller (factory set at 35°C) | – | Integrated mechanical thermostat | |
Compressor type | – | Rotative compressor | |
Noise level | dB(A) | 65 | |
Electrical connection | – | Three-pole connector | |
Protection degree EN60529/1 enclosure inside | – | IP55 | |
Protection degree EN60529/1 ambient inside | – | IP34 | |
Weight (with packaging) | Kg | 37(38) | |
Colour | – | RAL 7035 | |
Conformity/Certifications | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
2000W
IP-ACOWM200 – 2000W Outdoor Wall Mounted Air Conditioner
Features | Unit | IP-ACOWM200 |
---|---|---|
Power supply | V/Hz | 230V/1ph/50-60 |
Dimensions HxWxD | mm | 1000x400x240 |
Cooling capacity EN814 A35A35 | W | 2000/2100 |
Cooling capacity EN814 A35A50 | W | 1200/1250 |
Air flow rate (free blow) | ||
inside | m3/h | 600/625 |
outside | m3/h | 880/950 |
Max current | A | 6.6/6.9 |
Delayed fuse | A | 10 |
Absorbed electric power EN814 A35A35 | W | 1060/1100 |
Absorbed electric power EN814 A35A50 | W | 1240/1300 |
Refrigerant (type/charge) | g | R134a/450g |
Maximum Pressure | kPA | 2400 |
Operating temperature (ambient) | °C | +5/+50 |
Operating temperature (enclosure) | °C | +20/+45 |
Temperature controller (factory set at 35°C) | – | Integrated mechanical thermostat |
Compressor type-Alternative compressor | ||
Noise level | dB(A) | 70 |
Electrical connection | – | Three-pole connector |
Protection degree EN60529/1 enclosure inside | – | IP55 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | Kg | 49(50) |
Colour | – | RAL 7035 |
Conformity/Certifications | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
3000W
IP-ACOWM300 – 3000W Outdoor Wall Mounted Air Conditioner
IP-ACOWM400.0X- 4000W Outdoor Stainless Steel Wall Mounted Air Conditioner
Features | Unit | IP-ACOWM300/IP-ACOWM300.0X |
---|---|---|
Power supply | V/Hz | 400V/3ph/50-460X/3ph/60 |
Dimensions HxWxD | mm | 1500x400x255 |
Cooling capacity EN814 A35A35 | W | 2800/2950 |
Cooling capacity EN814 A35A50 | W | 2150/2330 |
Air flow rate (free blow) | ||
inside | m3/h | 600/625 |
outside | m3/h | 880/950 |
Max current | A | 2.2/2.6 |
Delayed fuse | A | 16 |
Absorbed electric power EN814 A35A35 | W | 2090/2200 |
Absorbed electric power EN814 A35A50 | W | 2400/2550 |
Refrigerant (type/charge) | g | R134a/450g |
Maximum Pressure | kPA | 2400 |
Operating temperature (ambient) | °C | +5/+50 |
Operating temperature (enclosure) | °C | +20/+45 |
Temperature controller (factory set at 35°C) | – | Integrated mechanical thermostat |
Compressor type-Alternative compressor | ||
Noise level | dB(A) | 70 |
Electrical connection | – | Three-pole connector |
Protection degree EN60529/1 enclosure inside | – | IP55 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | Kg | 49(50) |
Colour | – | RAL 7035 |
Conformity/Certifications | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
4000W
IP-ACOWM400 – 4000W Outdoor Wall Mounted Air Conditioner
IP-ACOWM400.0X- 4000W Outdoor Stainless Steel Wall Mounted Air Conditioner
Features | Unit | IP-ACOWM400/IP-ACOWM400.0X |
---|---|---|
Power supply | V/Hz | 400V/3ph/50-460X/3ph/60 |
Dimensions HxWxD | mm | 1500x400x255 |
Cooling capacity EN814 A35A35 | W | 3800/3890 |
Cooling capacity EN814 A35A50 | W | 2800/3160 |
Air flow rate (free blow) | ||
inside | m3/h | 600/625 |
outside | m3/h | 880/950 |
Max current | A | 2.7/3.0 |
Delayed fuse | A | 16 |
Absorbed electric power EN814 A35A35 | W | 2200/2320 |
Absorbed electric power EN814 A35A50 | W | 2600/2750 |
Refrigerant (type/charge) | g | R134a/450g |
Maximum Pressure | kPA | 2400 |
Operating temperature (ambient) | °C | +5/+50 |
Operating temperature (enclosure) | °C | +20/+45 |
Temperature controller (factory set at 35°C) | – | Integrated mechanical thermostat |
Compressor type-Alternative compressor | ||
Noise level | dB(A) | 70 |
Electrical connection | – | Three-pole connector |
Protection degree EN60529/1 enclosure inside | – | IP55 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | Kg | 49(50) |
Colour | – | RAL 7035 |
Conformity/Certifications | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
Indoor Roof-Mounted Air-Conditioner Details
Roof-mount compact air conditioners designed for the cooling needs of indoor electrical cabinets. They are optimised for roof mounting and have been designed for high efficiency and low maintenance.
500W
IP-ACIRM050 – 500W Indoor Roof Mounted Air Conditioner
Features | Unit | IP-ACIRM050 |
---|---|---|
Power supply | V/Hz | 230V/1ph/50-60 |
Dimensions HxWxD | mm | 250x500x350 |
Cooling capacity EN814 A35A35 | W | 500/520 |
Cooling capacity EN814 A35A50 | W | 360/380 |
Max running current | A | 2.0/2.2 |
Inrush current | A | 6.9/7.0 |
Absorbed electric power EN814 A35A35 | W | 360/420 |
Operating temperature (ambient) | °C | +20/+55 (50Hz)|+20/+50 (60Hz) |
Noise level | dB(A) | 67 |
Protection degree EN60529/1 enclosure inside | – | IP54 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | kg | 22 |
Colour | – | RAL 7035 |
Conformity | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
1000W
IP-ACIRM100 – 1000W Indoor Roof Mounted Air Conditioner
Features | Unit | IP-ACIRM100 |
---|---|---|
Power supply | V/Hz | 230V/1ph/50-60 |
Dimensions HxWxD | mm | 300x600x400 |
Cooling capacity EN814 A35A35 | W | 1000/1060 |
Cooling capacity EN814 A35A50 | W | 760/790 |
Max running current | A | 2.8/3.4 |
Inrush current | A | 11.5/12.6 |
Absorbed electric power EN814 A35A35 | W | 580/670 |
Operating temperature (ambient) | °C | +20/+55 (50Hz)|+20/+50 (60Hz) |
Noise level | dB(A) | 70 |
Protection degree EN60529/1 enclosure inside | – | IP54 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | kg | 37 |
Colour | – | RAL 7035 |
Conformity | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
1500W
IP-ACIRM150 – 1500W Indoor Roof Mounted Air Conditioner
Features | Unit | IP-ACIRM150 |
---|---|---|
Power supply | V/Hz | 230V/1ph/50-60 |
Dimensions HxWxD | mm | 300x600x400 |
Cooling capacity EN814 A35A35 | W | 1460/1520 |
Cooling capacity EN814 A35A50 | W | 1090/1130 |
Max running current | A | 4.0/4.8 |
Inrush current | A | 16.3/13.5 |
Absorbed electric power EN814 A35A35 | W | 790/930 |
Operating temperature (ambient) | °C | +20/+55 (50Hz)|+20/+50 (60Hz) |
Noise level | dB(A) | 70 |
Protection degree EN60529/1 enclosure inside | – | IP54 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | kg | 41 |
Colour | – | RAL 7035 |
Conformity | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |
2000W
IP-ACIRM200 – 2000W Indoor Roof Mounted Air Conditioner
Features | Unit | IP-ACIRM200 |
---|---|---|
Power supply | V/Hz | 230V/1ph/50-60 |
Dimensions HxWxD | mm | 400x800x400 |
Cooling capacity EN814 A35A35 | W | 2000/2110 |
Cooling capacity EN814 A35A50 | W | 1500/1570 |
Max running current | A | 5.1/6.2 |
Inrush current | A | 23.6/24.1 |
Absorbed electric power EN814 A35A35 | W | 1040/1250 |
Operating temperature (ambient) | °C | +20/+55 (50Hz)|+20/+50 (60Hz) |
Noise level | dB(A) | 65 |
Protection degree EN60529/1 enclosure inside | – | IP54 |
Protection degree EN60529/1 ambient inside | – | IP34 |
Weight (with packaging) | kg | 54 |
Colour | – | RAL 7035 |
Conformity | – | SAA, CE, AS/NZS60335.2.40:2019, AS/NZS60335.1:2020 |