Thermal Controllers for Electrical Enclosures
IP Enclosures provide a range of thermal control products for electrical enclosures. The range of controllers are suitable for use with IP Enclosures range of heating and cooling products. The range includes thermostats, hygrostats, electronic thermostat temperature controllers and fan speed controllers. Electrical enclosures may require cooling or heating to manage the internal climate within the external climate to mitigate risks of equipment failure. Cooling and heating units do not need to run continuously but need to be controlled to switch on and off to prevent overcooling or overheating and to manage energy consumption. Thermostats sense the temperature inside the enclosure in relation to a setpoint, which is either the minimum or maximum temperature that the enclosure should maintain. The thermostat will switch on and off climate protection products including fans and/or heaters. Hygrostats sense the relative humidity inside the enclosure. If the relative humidity rises above the setpoint, the contacts close to start the heater. Since warm air can hold more water vapor than cold air, the temperature increase caused by the heater causes the relative humidity to decrease. Manufacturers of electronics typically specify acceptable levels of relative humidity therefore set the hygrostat accordingly. If not specified, typically set the hygrostat to 70-75%. IP Enclosures thermal control products are manufactured to the highest quality in Italy.
Item | Specifications | SKU | Data Sheet | Step File |
---|---|---|---|---|
Thermostats | ||||
Thermostat for Heater | N/C -10°/+50°C | IP-THNC1 | .stp | |
Thermostat for Heater | NC 0/+60°C | IP-THNC2 | .stp | |
Thermostat for Heater | NC +20/+80°C | IP-THNC3 | .stp | |
Thermostat for Fan | NO -10/+50°C | IP-THNO1 | .stp | |
Thermostat for Fan | NO 0/+60°C | IP-THNO2 | .stp | |
Thermostat for Fan | NO +20/+80°C | IP-THNO3 | .stp | |
Double Thermostat for Fan & Heater | NC NO , -10/+50 +20/+80°C | IP-THD1 | .stp | |
Double Thermostat for Fan & Heater | NC NO , 0/+60 0/+60°C | IP-THD2 | .stp | |
Double Thermostat for Fan & Heater | NO NO , 0/+60 0/+60°C | IP-THD3 | .stp | |
Hygrostats | ||||
Mechanical Hygrostat | 10-90 RH% | IP-MH1 | .stp | |
Electronic Thermo-hygrostat | 0/+60°C , 30-90 RH% | IP-ETH1 | .stp |
Thermostats
Compact Thermostat for DIN 35mm rail mounting. Based on bimetallic junction, provides high capacity NO or NC contact.
NC Contact – Typically used for controlling heaters.
NO Contact – Typically used for controlling ventilation devices.
Features | Unit | IP-THNC1 |
---|---|---|
Contact function | – | NC |
Temperature setting range | °C | -10/+50 |
Precision | °C | ±4 |
Hysteresis | °C | 7 |
Max. switching current | – | |
250Vac resistive load (inductive load) | A | 10 (1.6) |
125Vac resistive load (ind. cos phi 0.6) | A | 15 (2.5) |
Max. switching power in Vdc | W | 30 |
Temperature sensor type | – | Thermostatic bimetal |
Contact type | – | Snap action |
Contact resistance | mOhm | < 10 |
Service life | cycles | >100.000 |
Electrical connections | – | 2-pole terminal for 2.5 mm² wire |
Casing | – | PA6; UL94 V0 self-estinguishing; light grey RAL 7035 |
Protection degree EN60529 | – | IP20 |
Operating temperature | °C (°F) | -25/+80 (-13/+176) |
Storage temperature | °C (°F) | -45/+80 (-49/+176) |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Installation position | – | Variable |
Conformity | – | CE – UL File n.E348803 |
Dimensions HxWxD | mm | 61x34x35 |
Weight | g | 48 |
Features | Unit | IP-THNC2 |
---|---|---|
Contact function | – | NC |
Temperature setting range | °C | 0/+60 |
Precision | °C | ±4 |
Hysteresis | °C | 7 |
Max. switching current | – | |
250Vac resistive load (inductive load) | A | 10 (1.6) |
125Vac resistive load (inductive load) | A | 15 (2.5) |
Max. switching power in Vdc | W | 30 |
Temperature sensor type | – | Thermostatic bimetal |
Contact type | – | Snap action |
Contact resistance | mOhm | < 10 |
Service life | cycles | > 100.000 |
Electrical connections | – | 2-pole teminal for poli 2.5 mm² |
Casing | – | PA6; UL94 V0 self-estinguishing; light grey RAL 7035 |
Protection degree EN60529 | – | IP20 |
Operating temperature | °C (°F) | -25/+80 (-13/+176) |
Storage temperature | °C (°F) | -45/+80 (-49/+176) |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Installation position | – | Variable |
Conformity | – | CE – UL File n.E348803 |
Dimensions HxWxD | mm | 61x34x35 |
Weight | g | 48 |
Features | Unit | IP-THNC3 |
---|---|---|
Contact function | – | NC |
Temperature setting range | °C | +20/+80 |
Precision | °C | ±4 |
Hysteresis | °C | 7 |
Max. switching current | – | |
250Vac resistive load (inductive load) | A | 10 (1.6) |
125Vac resistive load (inductive load) | A | 15 (2.5) |
Max. switching power in Vdc | W | 30 |
Temperature sensor type | – | Thermostatic bimetal |
Contact type | – | Snap action |
Contact resistance | mOhm | < 10 |
Service life | cycles | > 100.000 |
Electtrical connections | – | 2-pole terminal for 2.5 mm² wire |
Casing | – | PA6; UL94 V0 self-estinguishing; light grey RAL 7035 |
Protection degree EN60529 | – | IP20 |
Operating temperature | °C (°F) | -25/+80 (-13/+176) |
Storage temperature | °C (°F) | -45/+80 (-49/+176) |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Installation position | – | variable |
Conformity | – | CE – UL File n.E348803 |
Dimensions HxWxD | mm | 61x34x35 |
Weight | g | 48 |
Features | Unit | IP-THNO1 |
---|---|---|
Contact function | – | NO |
Temperature setting range | °C | -10/+50 |
Precision | °C | ±4 |
Hysteresis | °C | 7 |
Max. switching current | – | |
250Vac resistive load (inductive load) | A | 10 (1.6) |
125Vac resistive load (inductive load) | A | 15 (2.5) |
Max. switching power in Vdc | W | 30 |
Temperature Sensor type | – | Thermostatic bimetal |
Contact type | – | Snap action |
Contact resistance | mOhm | < 10 |
Service life | cycles | > 100.000 |
Electrical connections | – | 2-pole terminal for 2.5 mm² wire |
Casing | – | PA6 ; UL94 self-estinguishing ; light grey RAL 7035 |
Protection degree EN60529 | – | IP20 |
Operating Temperature | °C (°F) | -25/+80 (-13/+176) |
Storage Temperature | °C (°F) | -45/+80 (-49/+176) |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Installation position | – | variable |
Conformity | – | CE – UL File n.E348803 |
Dimensions HxWxD | mm | 61x34x35 |
Weight | g | 48 |
Features | Unit | IP-THNO2 | |
---|---|---|---|
Contact function | – | NO | |
Temperature setting range | °C | 0/+60 | |
Precision | °C | ±4 | |
Hysteresis | °C | 7 | |
Max.switching current | – | ||
250Vac resistive load (inductive load) | A | 10 (1.6) | |
125Vac resistive load (inductive load) | A | 15 (2.5) | |
Max. switching power in Vdc | W | 30 | |
Temperature sensor type | – | Thermostatic bimetal | |
Contact type | – | Snap action | |
Contact resistance | mOhm | < 10 | |
Service life | cycles | > 100 | 000 |
Electrical connections | – | 2-pole terminal for 2.5 mm² wire | |
Casing | – | PA6; UL self-estinguishing; light grey RAL 7035 | |
Protection degree EN60529 | – | IP20 | |
Operating temperature | °C (°F) | -25/+80 (-13/+176) | |
Storage Temperature | °C (°F) | -45/+80 (-49/+176) | |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 | |
Installation position | – | variable | |
Conformity | – | CE – UL File n.E348803 | |
Dimensions HxLxP | mm | 61x34x35 | |
Weight | g | 48 |
Features | Unit | IP-THNO3 |
---|---|---|
Contact function | – | NO |
Temperature setting range | °C | +20/+80 |
Precision | °C | ±4 |
Hysteresis | °C | 7 |
Max. switching current | – | |
250Vac resistive load (inductive load) | A | 10 (1.6) |
125Vac resistive load (inductive load) | A | 15 (2.5) |
Max. switching power in Vdc | W | 30 |
Temperature sensor type | – | Thermostatic bimetal |
Contact type | – | Snap action |
Contact resistance | mOhm | < 10 |
Service life | cycles | > 100.000 |
Electrical connections | – | 2-pole terminal for 2.5 mm² wire |
Casing | – | PA6; UL94 VO self-estinguisching; light grey RAL 7035 |
Protection degree EN60529 | – | IP20 |
Operating temperature | °C (°F) | -25/+80 (-13/+176) |
Storage temperature | °C (°F) | -45/+80 (-49/+176) |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Installation position | – | variable |
Conformity | – | CE – UL File n.E348803 |
Dimensions HxWxD | mm | 61x34x35 |
Weight | g | 48 |
Double Thermostats
Compact Double Thermostat for DIN 35mm rail mounting. Based on bimetallic junction, provides high capacity separated NO and NC contacts in various combinations.
Features | Unit | IP-THD1 |
---|---|---|
Contact function | – | NC | NO |
Temperature setting range | °C | -10/+50 | +20/+80 |
Precision | °C | ±4 |
Hysteresis | °C | 7 |
Max. switching current: | – | |
at 250Vac resistive load (inductive load) | A | 10 (1.6) |
at 125Vac resistive load (inductive load) | A | 15 (2.5) |
Max. switching power in Vdc | W | 30 |
Temperature sensor type | – | Thermostatic bimetal |
Contact type | – | Snap action |
Contact resistance | mOhm | < 10 |
Service life | cycles | > 100.000 |
Electrical connections | – | 2-pole terminal for 2.5 mm² wire |
Casing | – | PA6 ; UL94 V0 self-estinguishing ; light grey RAL 7035 |
Protection degree EN60529 | – | IP20 |
Operating temperature | °C(°F) | -25/+80 (-13/+176) |
Storage temperature | °C(°F) | -45/+80 (-49/+176) |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Installation position | – | variable |
Conformity | – | CE – UL File n.E348803 |
Dimensions HxWxD | mm | 61x53x35 |
Weight | g | 80 |
Features | Unit | IP-THD2 |
---|---|---|
Contact function | – | NC | NO |
Temperature setting range | °C | -0/+60 | +0/+60 |
Precision | °C | ±4 |
Hysteresis | °C | 7 |
Max. switching current: | – | |
at 250Vac resistive load (inductive load) | A | 10 (1.6) |
at 125Vac resistive load (inductive load) | A | 15 (2.5) |
Max. switching power in Vdc | W | 30 |
Temperature sensor type | – | Thermostatic bimetal |
Contact type | – | Snap action |
Contact resistance | mOhm | < 10 |
Service life | cycles | > 100.000 |
Electrical connections | – | 2-pole terminal for 2.5 mm² wire |
Casing | – | PA6; UL94 V0 self-estinguishing; light grey RAL 7035 |
Protection degree EN60529 | – | IP20 |
Operating temperature | °C(°F) | -25/+80 (-13/+176) |
Storage temperature | °C(°F) | -45/+80 (-49/+176) |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Installation position | – | variable |
Conformity | – | CE – UL File n.E348803 |
Dimensions HxWxD | mm | 61x53x35 |
Weight | g | 80 |
Features | Unit | IP-THD3 |
---|---|---|
Contact function | – | NO | NO |
Temperature setting range | °C | -0/+60 | +0/+60 |
Precision | °C | ±4 |
Hysteresis | °C | 7 |
Max. switching current: | – | |
at 250Vac resistive load (inductive load) | A | 10 (1.6) |
at 125Vac resistive load (inductive load) | A | 15 (2.5) |
Max. switching power in Vdc | W | 30 |
Temperature sensor type | – | Thermostatic bimetal |
Contact type | – | Snap action |
Contact resistence | mOhm | < 10 |
Service life | cycles | > 100.000 |
Electrical connections | – | 2-pole terminal for 2.5 mm² wire |
casing | – | PA6; UL94 VO self-estinguishing; light grey RAL 7035 |
Protection degree EN60529 | – | IP20 |
Operating temperature | °C(°F) | -25/+80 (-13/+176) |
Storage temperature | °C(°F) | -45/+80 (-49/+176) |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Installation position | – | variable |
Conformity | – | CE – UL File n.E348803 |
Dimensions HxWxD | mm | 61x53x35 |
Weight | g | 80 |
Hygrostats
Mechanical and electrical hygrostats for DIN 35 mm rail mounting. Typically used to control enclosure heaters.
Features | Unit | IP-MH1 |
---|---|---|
Relative Humidity setting range | RH% | 10-90 |
Relative Humidity Hysteresis | RH% 5 | (max 10) |
Precision | RH% | ±5 |
Max. switching current | ||
NC at 240Vac resistive load | A | 2.2 |
NC at 120Vac resistive load | A | 4.4 |
NO at 240Vac resistive load | A | 5 |
NO at 120Vac resistive load | A | 10 |
Electrical connections | – | 3-pole terminal for 2.5 mm² wire |
Contact type | – | Change over |
Casing | – | PA6; UL94 V0 self-estinguishing; light grey RAL 7035 |
Protection degree EN60529 | – | IP20 |
Operating temperature | °C (°F) | -10/+50 (+50/+122) |
Storage temperature | °C(°F) | -45/+80 (-49/+176) |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Installation position | – | Vertical |
Conformity | – | CE |
Dimensions HxWxD | mm | 91x54x48 |
Weight | g | 170 |
Thermo-Hygrostats
Electronic Hygrothermostat for DIN 35mm rail mounting. Typically used to control enclosure heaters. The change over contact triggers either for high humidity or low temperature, independently set adjustable with LED display of power on and status.
Features | Unit | IP-ETH1 |
---|---|---|
Power supply | V/Hz | 230/50-60 |
Temperature setting range | °C | 0/+60 |
Precision | °C | ±1 |
Temperature Hysteresis | °C | 2 |
Relative Humidity setting range | RH% | 30-90 |
Relative Humidity Hysteresis | % | 5 |
Reaction time | sec | 60 |
Max. switching current | ||
NO at 250Vac resistive load | A | 10 |
NO at 30Vdc resistive load | A | 8 |
NO at 240Vac motor load | Hp | 1/2 |
NO at 120Vac motor load | Hp | 1/4 |
NC at 250Vac resistive load | A | 10 |
NC at 30Vdc resistive load | A | 8 |
Contact type | – | Change over |
Contact resistance | mOhm | < 10 |
Service life n. cycles | cycles | > 100.000 |
Electrical connections | – | 5-pole terminal for 2.5 mm² wire |
Optical signal | – | LED |
Casing | – | PA6; UL94 V0 self-estinguishing; light grey RAL 7035 |
Protection degree EN60529 | – | IP20 |
Operating/Storage temperature | °C (°F) | -40/+80 (-40/+176) |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Installation position | – | Vertical |
Conformity | – | CE – UL FILE N. E348803 |
Dimensions HxWxD | mm | 68x53x38 |
Weight | g | 105 |
Fan Speed Controllers
Electronic temperature-regulated fan speed controller for DIN 35mm rail mounting. Helps to reduce fan noise by reducing air flow rate to optimum required speed.
Features | Unit | IP-FSC1 |
---|---|---|
Power supply | V/Hz | 100-230/50-60 |
Temperature setting range | °C | +20/+60 |
Fan speed setting range | % | 0-100 |
Speed controller | – | partialization of wave |
Input | – | NTC sensor |
Max. output fan | – | 300W (100-230/50-60Hz) |
Electrical connections | – | terminal for 2.5 mm² wire |
Optical signal | – | LED |
Casing | – | PA6; UL94 V0 self-estinguishing; light grey RAL 7035 |
Protection degree EN60529 | – | IP20 |
Operating/Storage temperature | °C (°F) | -10/+70 (+14/+158) |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Installation position | – | Vertical |
Conformity | – | CE |
Dimensions HxWxD | mm | 68x53x38 |
Weight | g | 105 |
Digital Electronic Temperature Controllers
Compact Size – 1 DIN Module (17,5mm) or 2 DIN modules (35mm). Digital adjustment of temperature. Appropriate for temperature control inside electric panel (fan and resistor control). NTC probe input, 1 or 2 relay outputs.
Features | Unit | IP-TC1 |
---|---|---|
Power supply | V | 200-240 VAC |
Input | – | NTC (10k – 25°C) |
Relay | – | 1 SPDT output (10A-AC1) |
Control | – | ON/OFF |
Overall accuracy | % | +/- 0.5 full scale |
Display resolution | – | 1 |
Measurement range | °C | NTC -20 ~ +65°C probe on the controller / NTC -35 ~ +99°C external probe |
Sampling rate | Hz | 12 |
Display | – | 2 red digit |
Parameters programming | – | by keyboard |
Operating temperature | °C | -20 ~ +65 |
Operating humidity (no condensate) | RH% | 30 ~ 95 |
Housing | – | self-extinguishing plastic |
Dimensions HxWxD | mm | 17.5x64x98mm – 1 Din rail module 35x64x98mm – 2 Din rail module |
Connessions | – | 2.5 mm² screw terminal block |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Conformity | – | CE |
Weight | g | 45 |
Features | Unit | IP-TC2 |
---|---|---|
Power supply | V | 200-240 VAC/DC |
Input | – | NTC (10k – 25°C) |
Relay | – | 2 SPDT outputs (10A-AC1) |
Control | – | ON/OFF |
Overall accuracy | % | +/- 0.5 full scale |
Display resolution | – | 1 |
Measurement range | °C | NTC -20 ~ +65°C probe on the controller / NTC -35 ~ +99°C external probe |
Sampling rate | Hz | 12 |
Display | – | 2 red digit |
Parameters programming | – | by keyboard |
Operating temperature | °C | -20 ~ +65 |
Operating humidity (no condensate) | RH% | 30 ~ 95 |
Housing | – | self-extinguishing plastic |
Dimensions HxWxD | mm | 35x64x98mm – 1 Din rail module 35x64x98mm – 2 Din rail module |
Connessions | – | 2.5 mm² screw terminal block |
Mounting | – | Clip for mounting on DIN rail 35 mm EN50022 |
Conformity | – | CE |
Weight | g | 70 |